Analysis of sixphase system for transmission line
Electrical system engineer forecast possibility introduced the transmission line the sixphase system to change system that the present is the doublecircuit threephase system. This is because application rate caused electricity consumer demands more urgent and increase. Revenue from past research, ob...
Saved in:
| Main Authors: | , |
|---|---|
| Format: | Conference or Workshop Item |
| Published: |
2008
|
| Subjects: | |
| Online Access: | http://eprints.uthm.edu.my/2218/ http://eprints.uthm.edu.my/2218/1/peoco%2D2024%2DFinal.pdf |
| Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
| Summary: | Electrical
system engineer forecast possibility
introduced the transmission line the sixphase
system to change
system that the present is the doublecircuit
threephase
system.
This is because application rate caused electricity consumer
demands more urgent and increase. Revenue from past research,
obtain the transmission line sixphase
system has several
advantages as transmission line voltage higher compared line
that the present. In case normal, the transmission line six phase
system get enhance the capability delivery as many as 73% over
line that the present, impact reduction corona and decline
magnetic field also succeed bring good to the environment. Small
development system use but afford enhance the capability line
space basis and transmission line features, this study is over
converging to analysis the design for transformer sixphase
system. Comparison by system count perunit
use MATLAB and
PSCAD/ EMTDC simulation implemented for both system.
Analysis of data carried out for parameters as value phase
difference, voltage, current and power in transmission line.
Apart from that assessment choose the best transformer design
for sixphase
system also implemented. From the analysis data
performed found line system six phase have successfully
produced ascendant as many as 73% in the division transmission
line over system double threephase
circuit. Apart from obtain
that the best connection six phase system to acquire stated
ascendant is deltawye
deltainverted
wye connection and
diametrical connection. |
|---|